[Chinese aluminum industry network] This specification is based on the "hard aluminum wire for overhead strands (GB/T17048-2009)" standard.

1 Scope This specification specifies the requirements, test methods, inspection rules, packaging, marking, storage and transportation of materials for the procurement of "hard aluminum wires for overhead stranded wires".

2 Reference standard GB/T3048.2-2007 Test methods for electrical properties of wire and cable - Part 2: Tests for resistivity of metallic materials (IEC 60498: 1974, MOD)

GB/T4909.3 Test methods for bare wires Part 3: Tensile tests GB/T4909.7 Test methods for bare wires Part 7: Winding tests 3 For calculation of hard aluminum lines For numerical calculations, use the following values for hard aluminum lines:

Resistivity at 20°C, Larger (nΩ·m) 28.264 (equivalent to 61.0% IACS)

Density at 20°C (kg/dm3) 2.703

Linear expansion coefficient (1/°C) 23310-6

Temperature coefficient of resistance at 20°C (1/°C) 0.00403

4 Requirements 4.1 Material The hard aluminum wire shall be made of aluminium of the required purity in order to achieve the mechanical and electrical properties specified in this standard. The content of aluminum should not be less than 99.5%.

4.2 Diameter and diameter tolerance The nominal diameter of the hard aluminum wire, in millimeters, accurate to two decimal places.

The difference between each measured value of the hard aluminum wire diameter and the nominal value shall not be greater than the corresponding value specified in Table 1.

Table 1 Diameter and diameter of hard aluminum wire Tolerance of nominal diameter d Tolerance d ≤ 3.00 ± 0.03

d>3.00+1%d

In order to check whether the diameter of the hard aluminum wire meets the above requirements, the diameter should be measured twice in the same cross-section and perpendicular to each other.

4.3 Couplings Hard aluminum wire is permitted to be fitted before being drawn later. However, if all of the following conditions are met, the finished hard aluminum wire also allows a connector:

a) A looped hard aluminum wire weighs 500kg or more;

The above is the Requirements and experiment of "hard aluminum wire for overhead strand" we have listed for you. You can submit the following form to obtain more industry information we provide for you.

You can visit our website or contact us, and we will provide the latest consultation and solutions

Share to:

Send Inquiry

Home> Industry Information> Requirements and experiment of "hard aluminum wire for overhead strand"
Related Products List

Home

Product

Phone

About Us

Inquiry

We will contact you immediately

Fill in more information so that we can get in touch with you faster

Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.

Send